TECHNICAL DATA
Specification : IEC 898- 1995 / IS 8828- 1996
Current Rating : 1 to 40 Amps.
Voltage Rating : As per standard can be operated at 230V or 240/415V AC
Breaking Capacity : 1cn Ultimate breaking capacity (O-CO Cycle)
Rating (A) Type Breaking Cap. (A)
1 to 40 1,2,3,4 P 10000
No. of Operating Cycles (O-C) : 50,000
Tripping Characteristics : B-Curve – The magnetic releases operate between 3 ln to 5 1n
C-Curve – The magnetic releases operate between 5 1n to 10 1n
Impulse withstand Voltage (Uimp.) : 6KV
Weight (g.) Approx. : Type 1P 2P 3P 4P  
  :   120g 242g 365g 485g  
Tropicalization : Treatment 2 (Relative Humidity 99% at 25% C)
Rated Frequency : 50Hz
Number of Poles : 1, 1+N, 2, 3, 3+N
Mounting : Standard 35mm Din Rail
Housing : Fire Retardent glass fibre reinforced polyster
Reference Temperature : 300C Can be Operated uoto +550C
Altitude : Upto 2000 meter above sea level
Power Loss Rating : 6A 10A 16A 20A 25A 32A 40A
w : 3.0 3.5 3.5 4.0 6.0 7.0 7.5
I P Category : IP 20
Energy Limiting Class : 3